6 Measuring Moisture Content
To assess the structural soundness of a construction in terms of moisture, the moisture conditions in this construction may require measurement. However, such measurements should always be supplemented by an assessment of the actual conditions based on practical experience.
The measurement methods available range from coarse initial assessments to manual measurements for use in stationary conditions, to computer simulations of non-stationary conditions (moisture conditions allowing for variation over time).
Knowledge about the parameters underlying the model is necessary before taking measurements. Typically, these would include the exterior and interior climate impact (such as temperature, relative humidity, and solar radiation) as well as material parameters. Generally, moisture calculations are relatively unreliable, particularly because those climate and material parameters which form part of the calculations are unreliable or unknown.
Material data are typically found in tables and, in some cases, may be obtained from the manufacturer.
6.1 Climatic Parameters
The optimal basis for climatic parameters is achieved with sustained measurements over a relevant extended period in the building in question. Usually, however, it will be necessary to use empirical figures for temperature conditions given the application of the building.
6.1.1 Indoor Climate
The moisture content can be determined by allowing the indoor water vapour content to follow that of the outdoors and adding an amount corresponding to the expected humidification (which will typically be 3–5 g/m3 for dwellings). In other cases, the humidification may be subject to assessment relative to the application.
For buildings using humidifiers or other forms of climate regulation, the available sizing data of the system should be used.
If none of these options are available, the values for the building’s humidification class can be used.
For refrigerated rooms, skating rinks, and cold stores, the available sizing data of the climate system should be used.
It will usually be sufficient to describe the parameters relative to the indoor climate with monthly values.
6.1.2 Outdoor Conditions
Outdoor conditions are more difficult to measure because they vary much more. One should decide whether to include solar heating. It is generally alright to ignore solar heating of exterior surfaces. The potential of drying out during summer or the risk of summer condensation cannot be assessed with any degree of accuracy.
On a calm sunny day, the temperature of a dark roof may reach 60–70 °C. Conversely, emissions to the cold atmosphere during calm clear periods can lower the exterior surface temperature to several degrees below that of the air.
Due to the very sharp and non-linear rise of the vapour pressure with temperature, even the briefest periods with intense solar impact and the resulting high outside surface temperatures can be very significant to the drying of a construction. Therefore, it is not entirely correct to apply seasonal mean values of the outside temperature, as this would not consider the effect of a surface warmed by solar heating.
In a coarse initial assessment, data on the outdoor climate can be limited to conditions in the coldest month. In Denmark, this is February and the temperature is typically –1.1 °C with an RH of 90 %.
6.1.3 Danish Design Reference Year
For calculations, notably computer simulations, far more data are required than for rough estimates. This is typically where the Danish Design Reference Year (DRY) is used. In addition to hourly values for a typical year with average conditions, it also contains extreme periods (Jensen & Lund, 1995). DRY was developed for the purpose of calculating the thermal conditions of buildings and it contains data on solar radiation, wind, and precipitation, which can be relevant for moisture content calculations.
When determining parameters for the outdoor climate, one can make configurations to the following parameters (in increasing order of realism):
The balance of humidification and dehumidification
Whether to take solar impact and emissions into account
The duration of outdoor temperature intervals
Humidification/Dehumidification Balance
Six-month or twelve-month mean values are used for outdoor air temperature and humidity.
Sun and Radiation
Monthly mean values are used for the outdoor surface temperature where solar irradiation and solar radiation are considered. The solar irradiation absorbed on an exterior surface with the relevant solar absorptance, tilt, and orientation must be determined. Furthermore, longwave emissions to the atmosphere and other visible surroundings should be assessed. This is achieved using the mean air vapour pressure.
Table 11 shows the mean air temperature and the calculated outdoor temperature of a dark horizontal building surface for each month in the Danish Design Reference Year (DRY). Furthermore, the mean outdoor vapour pressure for each month is shown.
Table 11. Monthly and annual average outdoor temperatures, outside temperatures of a dark horizontal building surface, and the outdoor vapour pressure (Rode, 1996)
Duration Intervals for Outdoor Temperatures
The hours of a year are subdivided into several temperature intervals according to outdoor temperatures (e.g., intervals of 5 degrees). Thus, each temperature interval is represented by several hours corresponding to the total duration over the year. The method is applicable based on both air temperature and interior surface temperature.
The temperature groups are used as calculation intervals and condensation and dehumidification amounts are determined based on the number of hours in each interval.
This means that the few hours with very high temperatures are represented. Much moisture is moved during these brief periods and the calculated climatic impact results will be very realistic. Consequently, no safety factor has been incorporated into the calculation method. It is a disadvantage that the intervals cannot be linked to the time of year when they occur.
This method of describing the outdoor climate requires a detailed method for determining outside surface temperatures.
Table 12 shows the duration of the outdoor air temperature and of the temperature of a dark horizontal building surface (based on the Danish Design Reference Year (DRY)).
Table 12. Total annual length of periods with specific temperatures of outdoor air and a dark horizontal building surface in intervals of 5 degrees (Rode, 1998).
6.2 Dew Point Method
In the dew point method, the dew point temperature of the air surrounding or within a construction with temperature conditions which may occur in the moisture-sensitive layers of the construction. If temperatures lower than dew point temperature are expected, the construction should be upgraded. This is illustrated by the example below.
6.2.1 Example of Dew Point Calculation
From the outside, a roof construction comprises a roofing membrane, plywood, vapour barrier, and ceiling cladding. If there is doubt as to the vapour barrier's tightness and performance, the assumption should be made that there may be equilibrium between the inside of the roof and the indoor air.
In wintry conditions, if the indoor is 20 °C with a 40 % RH, indoor air vapour pressure will be 0.4 · 2338 Pa = 935 Pa. The temperature on the plywood can be calculated as approx. 2 °C. To avoid mould growth on the plywood, relative humidity on the surface must be kept below 75 % (i.e., the vapour pressure on the plywood should not exceed 0.75 · pm (2 °C) = 0.75 · 706 Pa = 530 Pa).
Consequently, the expected vapour pressure of the indoor air exceeds the permissible level and there will be a risk of mould growing on the plywood.
If the improvement involves insulating the roof externally to raise the temperature of the plywood, sufficient insulation must be added to make the indoor air vapour pressure equal 75 % of the saturation vapour pressure at the new temperature.
pm at plywood = pindoor air/RHcritical = 935/0.75 = 1247 Pa (33)
This saturation vapour pressure exists at approx. 10.3 °C.
6.3 The Glaser Method
The Glaser calculation method for water vapour diffusion is a stationary calculation method applying the constant conditions on both sides of the construction. However, it is possible to calculate several periods with different constant conditions (such as monthly intervals). One can thus gain an overview of humidification and dehumidification. The method is described in DS/EN ISO 13788, Hygrothermal performance of building components and building elements - Internal surface temperature to avoid critical surface humidity and interstitial condensation – Calculation methods (Danish Standards, 2013). The description in this section is consistent with this norm.
To assess the moisture conditions over a whole year, calculations are made for each month.
It is advisable to transfer the Glaser method to a spread sheet, thereby facilitating calculations under various climatic conditions or construction types (see
www.sbi.dk/fugt for further information).
6.3.1 Temperature Distribution
Temperature plays a vital role for the moisture conditions in a construction and all calculations are thus preceded by determining the temperatures in the construction.
Peripheral Conditions
The outdoor temperature is set to the monthly mean value for the relevant month.
The indoor temperature is set according to the expected level relative to building usage.
The soil temperature near structures facing grade level is set to the annual mean value for the outdoor temperature.
Determining the Temperature
The temperature throughout the construction is determined by making proportionality calculations. The drop in temperature above a layer of material is relative to the thermal insulance factor of that layer. The proportional drop in temperature above a layer of the overall drop in temperature above the structure is therefore identical to the layer’s thermal insulance factor (Rm) relative to the total thermal insulance of the construction (∑R).
The drop in temperature (Δθm) above a layer m, is therefore calculated using the following formula:
\Delta\theta_m=\left(\frac{R_m}{\sum R}\right)\left(\theta_{\imaginaryI nde}-\theta_{ude}\right)(34)
Determining the Insulance Factor
The insulance factor of each separate layer is calculated as its thickness divided by its thermal conductivity. For several materials, the design thermal conductivity, which can be used for practical calculations, is found in Table 25 in Annex A.
For other materials and further information (e.g. on thermal conductivity and U-values), please see the website of the Varmeisoleringsforeningen (Thermal insulation Association)
www.vif-isolering.dk.
Determining the Thermal Resistance
There is a slight temperature difference between the inside and outside surfaces of the structure because the thermal contact between the surface and the ambient air is not ideal. A thermal resistance is therefore calculated on either side of the construction.
According to DS 418 (Danish Standards, 2011), the thermal resistance is set to:
0.04 m²K/W on the outside of a construction facing the atmosphere
0.13 m²K/W for interior surfaces with a max. deviation from the vertical of 30° (e.g., exterior walls)
0.10 m²K/W for interior surfaces if the heat flow travels upwards (e.g., ceilings)
0.17 m²K/W for interior surfaces if the heat flow travels downwards (e.g., floors)
The method underlying this is described in DS/EN ISO 13788 (Danish Standards, 2013). Note that the method only operates with these thermal surface insulance factors when calculating interstitial condensation inside a construction and surface condensation of doors and windows. When assessing surface condensation and risk of mould on non-transparent constructions, the thermal resistance is set at 0.25 m2K/W. This is done to be conservative, even at the riskiest spots, such as corners.
For soil-facing structures, the soil is included with an insulance factor as stated in DS 418.
Determining the Thermal Insulance Factor for Cavities
The thermal insulance factor for unvented airspaces inside a construction can be read directly from tables, which state the thermal insulance factor relative to the thickness of the airspace and the direction of the heat flow. If a cavity is vented to the outside via small openings, this slightly vented airspace is included with a thermal insulance factor corresponding to half of that for a similar non-vented airspace. For vertical cavities, a slightly vented airspace is defined as a cavity where the openings to the outside are between 5 and 15 cm² per metre of horizontal length (e.g., those evident in raked out perpends in an outer brickwall). For horizontal cavities, openings are spaced between 5 and 15 cm² per m² of surface area. If the openings are smaller than this, the cavity is considered unvented. The insulance factor of facings on the outside of slightly vented airspaces can be included up to a value of 0.15 m² K/W.
If the openings are bigger than the limits for a slightly vented cavity, the space is considered vented. In this case, the thermal insulance factor of the cavity and all the layers on the outward-facing side of the cavity (facing the outside surface) is given the same value as the inside thermal resistance for the construction in question.
Example Temperature Distribution Calculation
From the outside, an exterior wall consists of a 110 mm brick facing, 200 mm mineral wool (with a design thermal conductivity of 0,036 W/m·K), 100 mm cellular concrete, and 20 mm of rendering.
The temperatures come from the values in Table 4. The example shows the conditions in the month of October.
The calculation is performed using Table 13. It is filled in with available data on material thickness, thermal conductivity, known thermal insulance factors, and air temperatures on either side of the structure (marked in bold on the chart). The remaining insulance factors and then the drops in temperature above each separate layer can then be calculated. Finally, the temperatures in the boundary layers can be determined. The separate material layers are not subdivided. Regardless, DS/EN ISO 13788:2013 (Danish Standards, 2013) stipulates that each layer must have a max. insulance factor of 0.25 m2K/W.
The temperature distribution is outlined in Figure 52.
The heat loss through the construction [W/m²] can be calculated as the total drop in temperature divided by the total thermal insulance factor.
Table 13. Example calculation of the distribution of temperature through an exterior wall in October.